BLITZDUCTORconnect – Compact
- For protecting data bus interfaces as well as measuring and control circuits
- High discharge capacity of 3 kA (10/350 µs), 10 kA (8/20 µs)
- Max. impulse current carrying capability (8/20 µs) Imax up to 20 kA
- Low voltage protection level, also capable of protecting terminal equipment
- Fast and simple cable connection thanks to push-in connection technology
- High system availability thanks to fail-safe performance
- LifeCheck and visual status indication integrated in the module
- Simple remote signalling of the status with the help of an optional remote signalling unit
- Vibration and shock-tested for safe operation
Details
Push-in connection technology for simple and fast cable connection
Integrated indication for easy and fast maintenance
Approvals for use in intrinsically safe measuring circuits
Simple status message with monitoring unit for arrester groups
Part No. 927910 BCO CL2 B 180
GTIN 4013364411739, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
Technical data
| SPD class | A |
| Max. continuous operating voltage (d.c.) (UC ) | 180 V |
| Nominal current (IL ) | 1.2 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 0 ohms |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927922 BCO CL2 BE 12
GTIN 4013364411951, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | M |
| Max. continuous operating voltage (d.c.) (UC ) | 15 V |
| Nominal current at 70 °C (IL ) | 0.75 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 1 ohms |
| Cut-off frequency line-line (fG ) | 1.4 MHz |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927924 BCO CL2 BE 24
GTIN 4013364411968, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | M |
| Max. continuous operating voltage (d.c.) (UC ) | 33 V |
| Nominal current at 70 °C (IL ) | 0.75 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 1 ohms |
| Cut-off frequency line-line (fG ) | 3.4 MHz |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927925 BCO CL2 BE 48
GTIN 4013364411975, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | M |
| Max. continuous operating voltage (d.c.) (UC ) | 54 V |
| Nominal current at 70 °C (IL ) | 0.75 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 1 ohms |
| Cut-off frequency line-line (fG ) | 5 MHz |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927942 BCO CL2 BD 12
GTIN 4013364411777, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | L |
| Max. continuous operating voltage (d.c.) (UC ) | 15 V |
| Nominal current at 70 °C (IL ) | 0.75 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 1 ohms |
| Cut-off frequency line-line (fG ) | 2.6 MHz |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927944 BCO CL2 BD 24
GTIN 4013364411784, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | L |
| Max. continuous operating voltage (d.c.) (UC ) | 36 V |
| Nominal current at 70 °C (IL ) | 0.75 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 1 ohms |
| Cut-off frequency line-line (fG ) | 5.8 MHz |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927945 BCO CL2 BD 48
GTIN 4013364411807, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | L |
| Max. continuous operating voltage (d.c.) (UC ) | 56 V |
| Nominal current at 70 °C (IL ) | 0.75 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 1 ohms |
| Cut-off frequency line-line (fG ) | 7.2 MHz |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927970 BCO CL2 BE HF 5
GTIN 4013364411982, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
Technical data
| SPD class | M |
| Max. continuous operating voltage (d.c.) (UC ) | 8.5 V |
| Nominal current at 70 °C (IL ) | 0.75 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 1 ohms |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927971 BCO CL2 BD HF 5
GTIN 4013364411999, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | L |
| Max. continuous operating voltage (d.c.) (UC ) | 8.5 V |
| Nominal current at 70 °C (IL ) | 0.75 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 1 ohms |
| Cut-off frequency line-line (fG ) | 100 MHz |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |
BCO CL2 E
Space-saving, compact surge arrester with a width of 6 mm and push-in connection technology with status indication. Finely limiting, single-stage surge protection with powerful diodes for protecting two single cores sharing a common reference potential as well as unbalanced interfaces.
3 Products
Part No. 927987 BCO CL2 E 12
GTIN 4013364485754, Customs tariff No. (EU): 85363010, Gross weight: 55.94 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | W |
| Max. continuous operating voltage (d.c.) (UC ) | 15 V |
| Nominal current at 60 °C (IL ) | 10 A |
| Nominal current at 80 °C (IL ) | 6 A |
| C1 Total nominal discharge current (8/20 µs) (In ) | 3 kA |
| Series resistance per line | 0 ohms |
| Approvals | UL 497B, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927988 BCO CL2 E 24
GTIN 4013364485747, Customs tariff No. (EU): 85363010, Gross weight: 56.04 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | W |
| Max. continuous operating voltage (d.c.) (UC ) | 33 V |
| Nominal current at 60 °C (IL ) | 10 A |
| Nominal current at 80 °C (IL ) | 6 A |
| C1 Total nominal discharge current (8/20 µs) (In ) | 1.2 kA |
| Series resistance per line | 0 ohms |
| Approvals | UL 497B, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927989 BCO CL2 E 48
GTIN 4013364485761, Customs tariff No. (EU): 85363010, Gross weight: 36.58 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | W |
| Max. continuous operating voltage (d.c.) (UC ) | 58 V |
| Nominal current at 60 °C (IL ) | 10 A |
| Nominal current at 80 °C (IL ) | 6 A |
| C1 Total nominal discharge current (8/20 µs) (In ) | 0.8 kA |
| Series resistance per line | 0 ohms |
| Approvals | UL 497B, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927954 BCO CL4 BC 24
GTIN 4013364485730, Customs tariff No. (EU): 85363010, Gross weight: 80.10 g, PU: 1.00 pc(s)
Technical data
| SPD class | L |
| Max. continuous operating voltage (d.c.) (UC ) | 36 V |
| Nominal current at 80 °C (IL ) | 3 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 2.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 20 kA |
| Series resistance per line | 0 ohms |
| Approvals | UL 497B, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927408 BCO CL2 BD HC10A 24
GTIN 4013364463653, Customs tariff No. (EU): 85363010, Gross weight: 68.30 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | L |
| Max. continuous operating voltage (d.c.) (UC ) | 45 V |
| Nominal current at 80 °C (IL ) | 10 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 2.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 20 kA |
| Series resistance per line | 0 ohms |
| Approvals | UL 497B, SIL |
| *) For details, see: www.dehn-international.com | |
Part No. 927984 BCO CL2 BD EX 24
GTIN 4013364412002, Customs tariff No. (EU): 85363010, Gross weight: 57.86 g, PU: 1.00 pc(s)
PredecessorTechnical data
| SPD class | L |
| Max. continuous operating voltage (d.c.) (UC ) | 36 V |
| Nominal current at 80 °C (IL ) | 0.5 A |
| D1 Lightning impulse current (10/350 µs) per line (Iimp ) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In ) | 10 kA |
| Series resistance per line | 1 ohms |
| Cut-off frequency line-line (fG ) | 3.5 MHz |
| Approvals | ATEX, IECEx, CCC, SIL |
| *) For details, see: www.dehn-international.com | |