DEHNsite
Part No. 921078 DSIT S CSP DC 48
GTIN 4013364269958, Customs tariff No. (EU): 85363090, Gross weight: 137.40 g, PU: 1.00 pc(s)
Additional information
- 
                	CAD files
	                - 
                    	        921098.stp
	
    	                        You are not authorized to download 921098.stp
- 
                    	        921098.igs
	
    	                        You are not authorized to download 921098.igs
- 
                    	        921098.jt
	
    	                        You are not authorized to download 921098.jt
- 
                    	        921098.dwg
	
    	                        You are not authorized to download 921098.dwg
- 
                    	        921098m_E.dxf
	
    	                        You are not authorized to download 921098m_E.dxf
 
- 
                    	        921098.stp
	
    	                        
Technical data
| SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II | 
| Nominal voltage (d.c.) (UN ) | 48 V | 
| Nominal voltage (a.c.) (UN ) | 60 V (50 / 60 Hz) | 
| Max. continuous operating voltage (d.c.) (UC ) | 100 V | 
| Max. continuous operating voltage (a.c.) (UC ) | 75 V (50 / 60 Hz) | 
| Lightning impulse current (10/350 µs) (Iimp ) | 12.5 kA | 
| Specific energy (W/R) | 39.06 kJ/Ohm | 
| Nominal discharge current (8/20 µs) (In ) | 12.5 kA | 
| Max. discharge current (8/20 µs) (Imax ) | 60 kA | 
| Voltage protection level (UP ) | ≤ 0.4 kV | 
| Response time (tA ) | ≤ 25 ns | 
| Max. mains-side overcurrent protection | 160 A gG | 
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR ) | 25 kArms | 
| Operating temperature range (TU ) | -40 °C ... +80 °C | 
| Operating state / fault indication | green / red | 
| Number of ports | 1 | 
| Cross-sectional area (min.) | 1.5 mm2 solid / flexible | 
| Cross-sectional area (max.) | 35 mm2 stranded / 25 mm2 flexible | 
| For mounting on | 35 mm DIN rails acc. to EN 60715 | 
| Enclosure material | thermoplastic, gray, UL 94 V-0 | 
| Place of installation | indoor installation | 
| Degree of protection | IP 20 | 
| Capacity | 1 module(s), DIN 43880 | 
| Approvals | UL | 
| Test values according to UL 1449 | --------------------------------- | 
| – SPD classification according to UL 1449 | type 1 component assembly | 
| – Voltage Protection Rating (VPR) | 0,3 kV | 
| – Nominal discharge current (8/20µs) ( In ) | 20 kA | 
:quality(98)/www.dehn-international.com/store/f/62759610/HDVORSCHAU/921078.jpg) 
                                
                                :quality(98)/www.dehn-international.com/store/f/62759610/HDVORSCHAU/921078.jpg) 
                                    
                                        
                                    
                                    
                                :quality(98)/www.dehn-international.com/store/f/62759611/HDVORSCHAU/952070p.jpg) 
                                
                                :quality(98)/www.dehn-international.com/store/f/62759611/HDVORSCHAU/952070p.jpg) 
                                    
                                        :quality(98)/www.dehn-international.com/store/f/62759612/HDVORSCHAU/921078m_E.jpg) 
                                
                                :quality(98)/www.dehn-international.com/store/f/62759612/HDVORSCHAU/921078m_E.jpg) 
                                    
                                        