DEHNguard® modular (Y)PV SCI ...

  • Prewired modular complete unit for use in photovoltaic systems consisting of a base part and plug-in protection modules
  • Combined disconnection and short-circuiting device with safe electrical isolation in the protection module (patented SCI principle)
  • Tried and tested fault-resistant Y circuit of DEHNguard M YPV SCI ... (FM) prevents damage to the surge protective device in case of insulation faults in the generator circuit
  • Integrated d.c. fuse allows safe replacement of protection modules without arc formation
  • Tested to EN 50539-11
  • Suitable for use in all PV systems according to IEC 60364-7-712

Details

Three-step d.c. switching device (patented SCI principle)
lorem ipsum
lorem ipsum

Further informations


DEHNguard M YPV SCI ...

Modular multipole surge arrester with three-step d.c. switching device for use in PV systems

4 Products

Product No. 952513 DG M YPV SCI 150

GTIN: 4013364136663, Customs tariff No.: 85363030, Gross weight: 289.70 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M YPV SCI 150 surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 150 V d.c.
with three-step d.c. switching device, width: 3 modules
Fault indication
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: <= 150 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 0.8 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M YPV SCI 150
Part No.: 952513
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 150 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 10 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 20 kA
Voltage protection level (UP ) ≤ 0.8 kV
Approvals KEMA, UL, CSA

Product 952513 was added to Notepad.

4 Products

Product No. 952511 DG M YPV SCI 600

GTIN: 4013364127494, Customs tariff No.: 85363030, Gross weight: 312.30 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M YPV SCI 600 surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 600 V d.c.
with three-step d.c. switching device, width: 3 modules
Fault indication
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: <= 600 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 2.5 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M YPV SCI 600
Part No.: 952511
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 600 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 2.5 kV
Approvals KEMA, UL, CSA

Product 952511 was added to Notepad.

4 Products

Product No. 952510 DG M YPV SCI 1000

GTIN: 4013364126428, Customs tariff No.: 85363030, Gross weight: 361.40 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M YPV SCI 1000 surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 1000 V d.c.
with three-step d.c. switching device, width: 3 modules
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: <= 1000 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 4 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M YPV SCI 1000
Part No.: 952510
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 1000 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 4 kV
Approvals KEMA, UL, CSA

Product 952510 was added to Notepad.

4 Products

Product No. 952512 DG M YPV SCI 1200

GTIN: 4013364127951, Customs tariff No.: 85363030, Gross weight: 356.50 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M YPV SCI 1200 surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 1200 V d.c.
with three-step d.c. switching device, width: 3 modules
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: <= 1200 V d.c.
Total discharge current: 30 kA
Voltage protection level: <= 4.5 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M YPV SCI 1200
Part No.: 952512
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 1200 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 4.5 kV
Approvals KEMA, CSA

Product 952512 was added to Notepad.


DEHNguard M YPV SCI ... FM

Modular multipole surge arrester with three-step d.c. switching device for use in PV systems; with remote signalling contact for monitoring device (floating changeover contact).

4 Products

Product No. 952518 DG M YPV SCI 150 FM

GTIN: 4013364136670, Customs tariff No.: 85363030, Gross weight: 297.00 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M YPV SCI 150 FM surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 150 V d.c.
with three-step d.c. switching device, width: 3 modules
Fault indication
with remote signalling contact
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: <= 150 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 0.8 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M YPV SCI 150 FM
Part No.: 952518
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 150 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 10 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 20 kA
Voltage protection level (UP ) ≤ 0.8 kV
Approvals KEMA, UL, CSA
Type of remote signalling contact changeover contact

Product 952518 was added to Notepad.

4 Products

Product No. 952516 DG M YPV SCI 600 FM

GTIN: 4013364127500, Customs tariff No.: 85363030, Gross weight: 319.29 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

EHNguard M YPV SCI 600 FM surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 600 V d.c.
with three-step d.c. switching device, width: 3 modules
Fault indication
with remote signalling contact
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: <= 600 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 2.5 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M YPV SCI 600 FM
Part No.: 952516
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 600 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 2.5 kV
Approvals KEMA, UL, CSA
Type of remote signalling contact changeover contact

Product 952516 was added to Notepad.

4 Products

Product No. 952515 DG M YPV SCI 1000 FM

GTIN: 4013364126435, Customs tariff No.: 85363030, Gross weight: 343.90 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M YPV SCI 1000 FM surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 1000 V d.c.
with three-step d.c. switching device, width: 3 modules
Fault indication
with remote signalling contact
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: <= 1000 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 4 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M YPV SCI 1000 FM
Part No.: 952515
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 1000 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 4 kV
Approvals KEMA, UL, CSA
Type of remote signalling contact changeover contact

Product 952515 was added to Notepad.

4 Products

Product No. 952517 DG M YPV SCI 1200 FM

GTIN: 4013364127968, Customs tariff No.: 85363030, Gross weight: 359.30 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M YPV SCI 1200 FM surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 1200 V d.c.,
width: 3 modules
Fault indication
with remote signalling contact
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: <= 1200 V d.c.
Total discharge current: 30 kA
Voltage protection level: <= 4.5 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M YPV SCI 1200 FM
Part No.: 952517
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 1200 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 4.5 kV
Approvals KEMA, CSA
Type of remote signalling contact changeover contact

Product 952517 was added to Notepad.


DEHNguard S PV SCI ...

Modular single-pole surge arrester with three-step d.c. switching device for PV systems earthed on the d.c. side.

2 Products

Product No. 952551 DG S PV SCI 150

GTIN: 4013364136687, Customs tariff No.: 85363030, Gross weight: 197.50 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard S PV SCI 150 surge arrester
Modular and pluggable single-pole arrester
for use in photovoltaic systems up to 150 V d.c.
with three-step d.c. switching device, width: 2 modules
Fault indication
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: 150 V d.c.
Total discharge current: 20 kA
Voltage protection level: <= 0.8 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG S PV SCI 150
Part No.: 952551
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 150 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 10 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 20 kA
Voltage protection level (UP ) ≤ 0.8 kV
Approvals KEMA, UL, CSA

Product 952551 was added to Notepad.

2 Products

Product No. 952550 DG S PV SCI 600

GTIN: 4013364136502, Customs tariff No.: 85363030, Gross weight: 215.90 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard S PV SCI 600 surge arrester
Modular and pluggable single-pole arrester
for use in photovoltaic systems up to 600 V d.c.
with three-step d.c. switching device, width: 2 modules
Fault indication
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: 600 V d.c.
Total discharge current: 25 kA
Voltage protection level: <= 2.5 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG S PV SCI 600
Part No.: 952550
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 600 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 2.5 kV
Approvals KEMA, UL, CSA

Product 952550 was added to Notepad.


DEHNguard S PV SCI ... FM

Modular single-pole surge arrester with three-step d.c. switching device for PV systems earthed on the d.c. side; with remote signalling contact for monitoring device (floating changeover contact).

2 Products

Product No. 952556 DG S PV SCI 150 FM

GTIN: 4013364136694, Customs tariff No.: 85363030, Gross weight: 203.10 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard S PV SCI 150 FM surge arrester
Modular and pluggable single-pole arrester
for use in photovoltaic systems up to 150 V d.c.
with three-step d.c. switching device, width: 2 modules
with remote signalling contact
Fault indication
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: 150 V d.c.
Total discharge current: 20 kA
Voltage protection level: <= 0.8 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG S PV SCI 150 FM
Part No.: 952556
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 150 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 10 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 20 kA
Voltage protection level (UP ) ≤ 0.8 kV
Approvals KEMA, UL, CSA
Type of remote signalling contact changeover contact

Product 952556 was added to Notepad.

2 Products

Product No. 952555 DG S PV SCI 600 FM

GTIN: 4013364136519, Customs tariff No.: 85363030, Gross weight: 218.70 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard S PV SCI 600 FM surge arrester
Modular and pluggable single-pole arrester
for use in photovoltaic systems up to 600 V d.c.
with three-step d.c. switching device, width: 2 modules
with remote signalling contact
Fault indication
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
Safe electrical isolation in the protection module
Max. PV voltage: 600 V d.c.
Total discharge current: 25 kA
Voltage protection level: <= 2.5 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG S PV SCI 600 FM
Part No.: 952555
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 600 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 2.5 kV
Approvals KEMA, UL, CSA
Type of remote signalling contact changeover contact

Product 952555 was added to Notepad.


DEHNguard M PV2 SCI ... (FM)

Modular multipole surge arrester with three-step d.c. switching device for protecting two MPP inputs; for use in PV systems up to 1000 V; FM version with floating remote signalling contact.

2 Products

Product No. 952514 DG M PV2 SCI 1000

GTIN: 4013364224964, Customs tariff No.: 85363030, Gross weight: 588.00 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M PV2 SCI 1000 surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 1000 V d.c.
with three-step d.c. switching device, width: 5 modules
Fault indication
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
For protecting 2 MPP inputs
Safe electrical isolation in the protection module
Max. PV voltage: <= 1000 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 4 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M PV2 SCI 1000
Part No.: 952514
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 1000 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 4 kV
Approvals UL, KEMA

Product 952514 was added to Notepad.

2 Products

Product No. 952519 DG M PV2 SCI 1000 FM

GTIN: 4013364224971, Customs tariff No.: 85363030, Gross weight: 599.00 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M PV2 SCI 1000 FM surge arrester
Modular and pluggable multipole arrester
for use in photovoltaic systems up to 1000 V d.c.
with three-step d.c. switching device
with remote signalling contact, width: 5 modules
Fault indication
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
For protecting 2 MPP inputs
Safe electrical isolation in the protection module
Max. PV voltage: <= 1000 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 4 kV
Short-circuit current rating Iscpv: 10 kA

Brand: DEHN + SÖHNE
Type: DG M PV2 SCI 1000 FM
Part No.: 952519
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 1000 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 4 kV
Approvals UL, KEMA
Type of remote signalling contact changeover contact

Product 952519 was added to Notepad.


DEHNguard M SN1868

Modular multipole surge arrester with three-step d.c. switching device for protecting 3 MPP inputs; for PV systems with remote signalling contact for monitoring device (floating changeover contact).

1 Products

Product No. 999799 DG M PV2 SCI SN1868 FM

GTIN: 4013364328723, Customs tariff No.: 85363030, Gross weight: 598.30 g, VPE: 1.00 Stk

Predecessor

Images

Additional information

DEHNguard M PV2 SCI SN1868 FM surge arrester
Modular and pluggable multipole arrester for use in photovoltaic systems up to 1000 V d.c.
with three-step d.c. switching device
with remote signalling contact, width: 5 modules
Type 2 SPD according to EN 50539-11
For use in accordance with IEC 60364-7-712
For protecting 3 MPP inputs
Safe electrical isolation in the protection module
Max. PV voltage: <= 1000 V d.c.
Total discharge current: 40 kA
Voltage protection level: <= 4 kV
Short-circuit current rating Iscpv: 10 kA
Fault indication

Brand: DEHN + SÖHNE
Type: DG M PV2 SCI SN1868 FM
Part No.: 999799
or equivalent.

Certificates

Meta-Data

Technical data

SPD according to EN 50539-11 type 2
Max. PV voltage (UCPV ) 1000 V
Short-circuit current rating (ISCPV ) 10 kA
Nominal discharge current (8/20 µs) [(DC+/DC-) --> PE] (In ) 12.5 kA
Max. discharge current (8/20 µs) [(DC+/DC-) --> PE] (Imax ) 25 kA
Voltage protection level (UP ) ≤ 4 kV
Approvals UL, KEMA
Type of remote signalling contact changeover contact

Product 999799 was added to Notepad.


back to top

This website uses cookies to ensure you get the best experience on our website. Learn more